Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

Electrical Power Systems Quality, Second Edition phần 7 pdf
Nội dung xem thử
Mô tả chi tiết
island. Therefore, some means of direct transfer trip is generally
required to ensure that the generator disconnects from the system
when certain utility breakers operate.
A more normal connection of DG is to use power and power factor
control. This minimizes the risk of islanding. Although the DG no
longer attempts to regulate the voltage, it is still useful for voltage regulation purposes during constrained loading conditions by displacing
some active and reactive power. Alternatively, customer-owned DG
may be exploited simply by operating off-grid and supporting part or all
of the customer’s load off-line. This avoids interconnection issues and
provides some assistance to voltage regulation by reducing the load.
The controls of distributed sources must be carefully coordinated
with existing line regulators and substation LTCs. Reverse power flow
can sometimes fool voltage regulators into moving the tap changer in
the wrong direction. Also, it is possible for the generator to cause regulators to change taps constantly, causing early failure of the tap-changing mechanism. Fortunately, some regulator manufacturers have
anticipated these problems and now provide sophisticated microcomputer-based regulator controls that are able to compensate.
To exploit dispersed sources for voltage regulation, one is limited in
options to the types of devices with steady, controllable outputs such as
reciprocating engines, combustion turbines, fuel cells, and battery storage. Randomly varying sources such as wind turbines and photovoltaics are unsatisfactory for this role and often must be placed on a
relatively stiff part of the system or have special regulation to avoid
voltage regulation difficulties. DG used for voltage regulation must
also be large enough to accomplish the task.
Not all technologies are suitable for regulating voltage. They must be
capable of producing a controlled amount of reactive power.
Manufacturers of devices requiring inverters for interconnection sometimes program the inverter controls to operate only at unity power factor
while grid-connected. Simple induction generators consume reactive
power like an induction motor, which can cause low voltage.
7.7 Flicker*
Although voltage flicker is not technically a long-term voltage variation, it is included in this chapter because the root cause of problems is
the same: The system is too weak to support the load. Also, some of the
solutions are the same as for the slow-changing voltage regulation
problems. The voltage variations resulting from flicker are often within
the normal service voltage range, but the changes are sufficiently rapid
to be irritating to certain end users.
316 Chapter Seven
*This section was contributed by Jeff W. Smith.
Long-Duration Voltage Variations
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
Flicker is a relatively old subject that has gained considerable
attention recently due to the increased awareness of issues concerning power quality. Power engineers first dealt with flicker in the
1880s when the decision of using ac over dc was of concern.2 Low-frequency ac voltage resulted in a “flickering” of the lights. To avoid this
problem, a higher 60-Hz frequency was chosen as the standard in
North America.
The term flicker is sometimes considered synonymous with voltage
fluctuations, voltage flicker, light flicker, or lamp flicker. The phenomenon being referred to can be defined as a fluctuation in system voltage
that can result in observable changes (flickering) in light output.
Because flicker is mostly a problem when the human eye observes it, it
is considered to be a problem of perception.
In the early 1900s, many studies were done on humans to determine observable and objectionable levels of flicker. Many curves, such
as the one shown in Fig. 7.14, were developed by various companies
to determine the severity of flicker. The flicker curve shown in Fig.
7.14 was developed by C. P. Xenis and W. Perine in 1937 and was
based upon data obtained from 21 groups of observers. In order to
account for the nature of flicker, the observers were exposed to various waveshape voltage variations, levels of illumination, and types of
lighting.3
Long-Duration Voltage Variations 317
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0.1 1.0 10.0 100.0
Frequency of Flicker in Seconds
Voltage Change (in Volts) on 120-V System
Threshold of Perception
Threshold of Objection
Figure 7.14 General flicker curve.
Long-Duration Voltage Variations
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
Flicker can be separated into two types: cyclic and noncyclic. Cyclic
flicker is a result of periodic voltage fluctuations on the system, while
noncyclic is a result of occasional voltage fluctuations.
An example of sinusoidal-cyclic flicker is shown in Fig. 7.15. This
type of flicker is simply amplitude modulation where the main signal
(60 Hz for North America) is the carrier signal and flicker is the modulating signal. Flicker signals are usually specified as a percentage of
the normal operating voltage. By using a percentage, the flicker signal
is independent of peak, peak-to-peak, rms, line-to-neutral, etc.
Typically, percent voltage modulation is expressed by
Percent voltage modulation 100%
where Vmax maximum value of modulated signal
Vmin minimum value of modulated signal
V0 average value of normal operating voltage
The usual method for expressing flicker is similar to that of percent
voltage modulation. It is usually expressed as a percent of the total
change in voltage with respect to the average voltage (V/V) over a certain period of time.
Vmax Vmin
V0
318 Chapter Seven
–200
–150
–100
–50
0
50
100
150
200
0.000
0.058
0.117
0.175
0.233
0.292
0.350
0.408
0.467
0.525
0.583
0.642
0.700
0.758
0.817
0.875
0.933
Time (s)
Voltage (V)
Figure 7.15 Example flicker waveform.
Long-Duration Voltage Variations
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
The frequency content of flicker is extremely important in determining whether or not flicker levels are observable (or objectionable).
Describing the frequency content of the flicker signal in terms of modulation would mean that the flicker frequency is essentially the frequency of the modulating signal. The typical frequency range of
observable flicker is from 0.5 to 30.0 Hz, with observable magnitudes
starting at less than 1.0 percent.
As shown in Fig. 7.14, the human eye is more sensitive to luminance
fluctuations in the 5- to 10-Hz range. As the frequency of flicker
increases or decreases away from this range, the human eye generally
becomes more tolerable of fluctuations.
One issue that was not considered in the development of the traditional flicker curve is that of multiple flicker signals. Generally, most
flicker-producing loads contain multiple flicker signals (of varying
magnitudes and frequencies), thus making it very difficult to accurately quantify flicker using flicker curves.
7.7.1 Sources of flicker
Typically, flicker occurs on systems that are weak relative to the
amount of power required by the load, resulting in a low short-circuit
ratio. This, in combination with considerable variations in current over
a short period of time, results in flicker. As the load increases, the current in the line increases, thus increasing the voltage drop across the
line. This phenomenon results in a sudden reduction in bus voltage.
Depending upon the change in magnitude of voltage and frequency of
occurrence, this could result in observable amounts of flicker. If a lighting load were connected to the system in relatively close proximity to
the fluctuating load, observers could see this as a dimming of the lights.
A common situation, which could result in flicker, would be a large
industrial plant located at the end of a weak distribution feeder.
Whether the resulting voltage fluctuations cause observable or objectionable flicker is dependent upon the following parameters:
■ Size (VA) of potential flicker-producing source
■ System impedance (stiffness of utility)
■ Frequency of resulting voltage fluctuations
A common load that can often cause flicker is an electric arc furnace
(EAF). EAFs are nonlinear, time-varying loads that often cause large
voltage fluctuations and harmonic distortion. Most of the large current
fluctuations occur at the beginning of the melting cycle. During this
period, pieces of scrap steel can actually bridge the gap between the electrodes, resulting in a highly reactive short circuit on the secondary side
Long-Duration Voltage Variations 319
Long-Duration Voltage Variations
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
of the furnace transformer. This meltdown period can generally result in
flicker in the 1.0- to 10.0-Hz range. Once the melting cycle is over and the
refining period is reached, stable arcs can usually be held on the electrodes resulting in a steady, three-phase load with high power factor.4
Large induction machines undergoing start-up or widely varying
load torque changes are also known to produce voltage fluctuations on
systems. As a motor is started up, most of the power drawn by the
motor is reactive (see Fig. 7.16). This results in a large voltage drop
across distribution lines. The most severe case would be when a motor
is started across the line. This type of start-up can result in current
drawn by the motor up to multiples of the full load current.
An example illustrating the impact motor starting and torque changes
can have on system voltage is shown in Fig. 7.17. In this case, a large
industrial plant is located at the end of a weak distribution feeder. Within
the plant are four relatively large induction machines that are frequently
restarted and undergo relatively large load torque variations.5
Although starting large induction machines across the line is generally not a recommended practice, it does occur. To reduce flicker, large
motors are brought up to speed using various soft-start techniques
such as reduced-voltage starters or variable-speed drives.
In certain circumstances, superimposed interharmonics in the supply voltage can lead to oscillating luminous flux and cause flicker.
Voltage interharmonics are components in the harmonic spectrum that
are noninteger multiples of the fundamental frequency. This phenomenon can be observed with incandescent lamps as well as with fluorescent lamps. Sources of interharmonics include static frequency
converters, cycloconverters, subsynchronous converter cascades,
induction furnaces, and arc furnaces.6
320 Chapter Seven
1.0 0.9 0.8 0.7 0.6 0.5
Slip
0.4 0.3 0.2 0.1 0.0
Active Power
Reactive Power
Q
P
Figure 7.16 Active and reactive power during induction machine
start-up.
Long-Duration Voltage Variations
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.