Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

Electrical Power Systems Quality, Second Edition phần 2 ppsx
Nội dung xem thử
Mô tả chi tiết
causing a voltage sag with duration of more than 1 cycle occurs within
the area of vulnerability. However, faults outside this area will not
cause the voltage to drop below 0.5 pu. The same discussion applies to
the area of vulnerability for ASD loads. The less sensitive the equipment, the smaller the area of vulnerability will be (and the fewer times
sags will cause the equipment to misoperate).
3.2.3 Transmission system sag
performance evaluation
The voltage sag performance for a given customer facility will depend on
whether the customer is supplied from the transmission system or from
the distribution system. For a customer supplied from the transmission
system, the voltage sag performance will depend on only the transmission
system fault performance. On the other hand, for a customer supplied
from the distribution system, the voltage sag performance will depend on
the fault performance on both the transmission and distribution systems.
This section discusses procedures to estimate the transmission system contribution to the overall voltage sag performance at a facility.
Section 3.2.4 focuses on the distribution system contribution to the
overall voltage sag performance.
Transmission line faults and the subsequent opening of the protective devices rarely cause an interruption for any customer because of
the interconnected nature of most modern-day transmission networks.
These faults do, however, cause voltage sags. Depending on the equipment sensitivity, the unit may trip off, resulting in substantial monetary losses. The ability to estimate the expected voltage sags at an
end-user location is therefore very important.
Most utilities have detailed short-circuit models of the interconnected transmission system available for programs such as ASPEN*
One Liner (Fig. 3.7). These programs can calculate the voltage throughout the system resulting from faults around the system. Many of them
can also apply faults at locations along the transmission lines to help
calculate the area of vulnerability at a specific location.
The area of vulnerability describes all the fault locations that can
cause equipment to misoperate. The type of fault must also be considered in this analysis. Single-line-to-ground faults will not result in the
same voltage sag at the customer equipment as a three-phase fault.
The characteristics at the end-use equipment also depend on how the
voltages are changed by transformer connections and how the equipment is connected, i.e., phase-to-ground or phase-to-phase. Table 3.1
summarizes voltages at the customer transformer secondary for a single-line-to-ground fault at the primary.
Voltage Sags and Interruptions 51
*Advanced Systems for Power Engineering, Inc.; www.aspeninc.com.
Voltage Sags and Interruptions
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
The relationships in Table 3.1 illustrate the fact that a single-lineto-ground fault on the primary of a delta-wye grounded transformer
does not result in zero voltage on any of the phase-to-ground or
phase-to-phase voltages on the secondary of the transformer. The
magnitude of the lowest secondary voltage depends on how the
equipment is connected:
■ Equipment connected line-to-line would experience a minimum voltage of 33 percent.
■ Equipment connected line-to-neutral would experience a minimum
voltage of 58 percent.
This illustrates the importance of both transformer connections and
the equipment connections in determining the actual voltage that
equipment will experience during a fault on the supply system.
Math Bollen16 developed the concept of voltage sag “types” to describe
the different voltage sag characteristics that can be experienced at the
end-user level for different fault conditions and system configurations.
The five types that can commonly be experienced are illustrated in Fig.
3.8. These fault types can be used to conveniently summarize the
52 Chapter Three
Figure 3.7 Example of modeling the transmission system in a short-circuit program for
calculation of the area of vulnerability.
Voltage Sags and Interruptions
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
Voltage Sags and Interruptions 53
0.58 1.00 0.58 0.00 1.00 1.00
0.58 1.00 0.58 0.33 0.88 0.88
0.33 0.88 0.88 — — —
0.88 0.88 0.33 0.58 1.00 0.58
TABLE 3.1 Transformer Secondary Voltages with a Single-Line-to-Ground
Fault on the Primary
Transformer
connection Phase-to-phase Phase-to-neutral Phasor
(primary/secondary) Vab Vbc Vca Van Vbn Vcn diagram
Sag Type D
One-phase
sag, phase
shift
Sag Type B
One-phase
sag, no phase
shift
Phase
Shift
Angle
None
Sag Type C
Two-phase
sag, phase
shift
Sag Type E
Two-phase
sag, no phase
shift
Sag Type A
Three-phase
sag
Note: Three-phase sags
should lead to relatively
balanced conditions;
therefore, sag type A is a
sufficient characterization
for all three-phase sags.
Number of Phases
12 3
Figure 3.8 Voltage sag types at end-use equipment that result from different types of
faults and transformer connections.
Voltage Sags and Interruptions
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
expected performance at a customer location for different types of
faults on the supply system.
Table 3.2 is an example of an area of vulnerability listing giving all the
fault locations that can result in voltage sags below 80 percent at the customer equipment (in this case a customer with equipment connected
line-to-line and supplied through one delta-wye transformer from the
transmission system Tennessee 132-kV bus). The actual expected performance is then determined by combining the area of vulnerability with
the expected number of faults within this area of vulnerability.
The fault performance is usually described in terms of faults per 100
miles/year (mi/yr). Most utilities maintain statistics of fault performance at all the different transmission voltages. These systemwide
statistics can be used along with the area of vulnerability to estimate
the actual expected voltage sag performance. Figure 3.9 gives an example of this type of analysis. The figure shows the expected number of
voltage sags per year at the customer equipment due to transmission
system faults. The performance is broken down into the different sag
types because the equipment sensitivity may be different for sags that
affect all three phases versus sags that only affect one or two phases.
3.2.4 Utility distribution system sag
performance evaluation
Customers that are supplied at distribution voltage levels are impacted
by faults on both the transmission system and the distribution system.
The analysis at the distribution level must also include momentary
interruptions caused by the operation of protective devices to clear the
faults.7 These interruptions will most likely trip out sensitive equipment. The example presented in this section illustrates data requirements and computation procedures for evaluating the expected voltage
sag and momentary interruption performance. The overall voltage sag
performance at an end-user facility is the total of the expected voltage
sag performance from the transmission and distribution systems.
Figure 3.10 shows a typical distribution system with multiple feeders and fused branches, and protective devices. The utility protection
scheme plays an important role in the voltage sag and momentary
interruption performance. The critical information needed to compute
voltage sag performance can be summarized as follows:
■ Number of feeders supplied from the substation.
■ Average feeder length.
■ Average feeder reactance.
■ Short-circuit equivalent reactance at the substation.
54 Chapter Three
Voltage Sags and Interruptions
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
Voltage Sags and Interruptions 55
TABLE 3.2 Calculating Expected Sag Performance at a Specific
Customer Site for a Given Voltage Level
Voltage at
Bus monitored
Fault type Faulted bus voltage bus (pu) Sag type
3LG Tennessee 132 0 A
3LG Nevada 132 0.23 A
3LG Texas 132 0.33 A
2LG Tennessee 132 0.38 C
2LG Nevada 132 0.41 C
3LG Claytor 132 0.42 A
1LG Tennessee 132 0.45 D
2LG Texas 132 0.48 C
3LG Glen Lyn 132 0.48 A
3LG Reusens 132 0.5 A
1LG Nevada 132 0.5 D
L-L Tennessee 132 0.5 C
2LG Claytor 132 0.52 C
L-L Nevada 132 0.52 C
L-L Texas 132 0.55 C
2LG Glen Lyn 132 0.57 C
L-L Claytor 132 0.59 C
3LG Arizona 132 0.59 A
2LG Reusens 132 0.59 C
1LG Texas 132 0.6 D
L-L Glen Lyn 132 0.63 C
1LG Claytor 132 0.63 D
L-L Reusens 132 0.65 C
3LG Ohio 132 0.65 A
1LG Glen Lyn 132 0.67 D
1LG Reusens 132 0.67 D
2LG Arizona 132 0.67 C
2LG Ohio 132 0.7 C
L-L Arizona 132 0.7 C
3LG Fieldale 132 0.72 A
L-L Ohio 132 0.73 C
2LG Fieldale 132 0.76 C
3LG New Hampshire 33 0.76 A
1LG Ohio 132 0.77 D
3LG Vermont 33 0.77 A
L-L Fieldale 132 0.78 C
1LG Arizona 132 0.78 D
2LG Vermont 33 0.79 C
L-L Vermont 33 0.79 C
3LG Minnesota 33 0.8 A
Voltage Sags and Interruptions
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.