Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

Electrical Power Systems Quality, Second Edition phần 5 pps
Nội dung xem thử
Mô tả chi tiết
range of power system equipment, most notably capacitors, transformers, and motors, causing additional losses, overheating, and overloading. These harmonic currents can also cause interference with
telecommunication lines and errors in power metering. Sections 5.10.1
through 5.10.5 discuss impacts of harmonic distortion on various power
system components.
5.10.1 Impact on capacitors
Problems involving harmonics often show up at capacitor banks first.
As discussed in Secs. 5.9.3 and 5.9.4, a capacitor bank experiences high
voltage distortion during resonance. The current flowing in the capacitor bank is also significantly large and rich in a monotonic harmonic.
Figure 5.32 shows a current waveform of a capacitor bank in resonance
with the system at the 11th harmonic. The harmonic current shows up
distinctly, resulting in a waveform that is essentially the 11th harmonic riding on top of the fundamental frequency. This current waveform typically indicates that the system is in resonance and a capacitor
bank is involved. In such a resonance condition, the rms current is typically higher than the capacitor rms current rating.
IEEE Standard for Shunt Power Capacitors (IEEE Standard 18-
1992) specifies the following continuous capacitor ratings:
■ 135 percent of nameplate kvar
■ 110 percent of rated rms voltage (including harmonics but excluding
transients)
■ 180 percent of rated rms current (including fundamental and harmonic current)
■ 120 percent of peak voltage (including harmonics)
Table 5.1 summarizes an example capacitor evaluation using a computer spreadsheet that is designed to help evaluate the various capacitor duties against the standards.
The fundamental full-load current for the 1200-kvar capacitor bank
is determined from
IC 50.2 A
The capacitor is subjected principally to two harmonics: the fifth and
the seventh. The voltage distortion consists of 4 percent fifth and 3 percent seventh. This results in 20 percent fifth harmonic current and 21
percent seventh harmonic current. The resultant values all come out
1200
3 13.8
kvar3
3 kVLL
210 Chapter Five
Fundamentals of Harmonics
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
well below standard limits in this case, as shown in the box at the bottom of Table 5.1.
5.10.2 Impact on transformers
Transformers are designed to deliver the required power to the connected loads with minimum losses at fundamental frequency.
Harmonic distortion of the current, in particular, as well as of the voltage will contribute significantly to additional heating. To design a
transformer to accommodate higher frequencies, designers make different design choices such as using continuously transposed cable
instead of solid conductor and putting in more cooling ducts. As a general rule, a transformer in which the current distortion exceeds 5 percent is a candidate for derating for harmonics.
There are three effects that result in increased transformer heating
when the load current includes harmonic components:
1. RMS current. If the transformer is sized only for the kVA requirements of the load, harmonic currents may result in the transformer
rms current being higher than its capacity. The increased total rms
current results in increased conductor losses.
2. Eddy current losses. These are induced currents in a transformer
caused by the magnetic fluxes. These induced currents flow in the
windings, in the core, and in other conducting bodies subjected to
the magnetic field of the transformer and cause additional heating.
This component of the transformer losses increases with the square
of the frequency of the current causing the eddy currents. Therefore,
Fundamentals of Harmonics 211
0 10 20 30
–200
–150
–100
–50
0
50
100
150
200
Time (ms)
Current (A)
Figure 5.32 Typical capacitor current from a system in 11th-harmonic resonance.
Fundamentals of Harmonics
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
this becomes a very important component of transformer losses for
harmonic heating.
3. Core losses. The increase in core losses in the presence of harmonics will be dependent on the effect of the harmonics on the applied
voltage and the design of the transformer core. Increasing the voltage distortion may increase the eddy currents in the core laminations. The net impact that this will have depends on the thickness of
212 Chapter Five
Recommended Practice for Establishing Capacitor Capabilities
When Supplied by Nonsinusoidal Voltages IEEE Std 18-1980
Capacitor Bank Data:
Bank Rating: 1200 kVAr
Voltage Rating: 13800 V (L-L)
Operating Voltage: 13800 V (L-L)
Supplied Compensation: 1200 kVAr
Fundamental Current Rating: 50.2 Amps
Fundamental Frequency: 60 Hz
Capacitive Reactance: 158.700 Ω
Harmonic Distribution of Bus Voltage:
Harmonic
Number
Frequency
(Hertz)
Volt Mag Vh (% of Fund.)
Volt Mag Vh (Volts)
Line Current Ih (% of Fund.)
1 60 100.00 7967.4 100.00
3 180 0.00 0.0 0.00
5 300 4.00 318.7 20.00
7 420 3.00 239.0 21.00
11 660 0.00 0.0 0.00
13 780 0.00 0.0 0.00
17 1020 0.00 0.0 0.00
19 1140 0.00 0.0 0.00
21 1260 0.00 0.0 0.00
23 1380 0.00 0.0 0.00
25 1500 0.00 0.0 0.00
Voltage Distortion (THD): 5.00 %
RMS Capacitor Voltage: 7977.39 Volts
Capacitor Current Distortion: 29.00 %
RMS Capacitor Current: 52.27 Amps
Capacitor Bank Limits:
Calculated Limit Exceeds Limit
Peak Voltage: 107.0% 120% No
RMS Voltage: 100.1% 110% No
RMS Current: 104.1% 180% No
kVAr: 104.3% 135% No
TABLE 5.1 Example Capacitor Evaluation
Fundamentals of Harmonics
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
the core laminations and the quality of the core steel. The increase
in these losses due to harmonics is generally not as critical as the
previous two.
Guidelines for transformer derating are detailed in ANSI/IEEE
Standard C57.110-1998, Recommended Practice for Establishing
Transformer Capability When Supplying Nonsinusoidal Load
Currents. The common K factor used in the power quality field for
transformer derating is also included in Table 5.2.2
The analysis represented in Table 5.2 can be summarized as follows.
The load loss PLL can be considered to have two components: I2R loss
and eddy current loss PEC:
PLL I2
R PECW (5.27)
The I2R loss is directly proportional to the rms value of the current.
However, the eddy current is proportional to the square of the current
and frequency, which is defined by
PEC KEC I2 h2 (5.28)
where KEC is the proportionality constant.
The per-unit full-load loss under harmonic current conditions is
given by
PLL ∑ Ih
2 (∑ Ih
2 h2 ) PEC R (5.29)
where PEC R is the eddy current loss factor under rated conditions.
The K factor3 commonly found in power quality literature concerning
transformer derating can be defined solely in terms of the harmonic
currents as follows:
Fundamentals of Harmonics 213
TABLE 5.2 Typical Values of PEC R
Type MVA Voltage PEC R, %
Dry 1 — 3–8
1.5 5 kV HV 12–20
1.5 15 kV HV 9–15
Oil-filled 2.5 480 V LV 1
2.5–5 480 V LV 1–5
5 480 V LV 9–15
Fundamentals of Harmonics
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
K (5.30)
Then, in terms of the K factor, the rms of the distorted current is
derived to be
∑ Ih 2 (pu) (5.31)
where PEC R eddy current loss factor
h harmonic number
Ih harmonic current
Thus, the transformer derating can be estimated by knowing the perunit eddy current loss factor. This factor can be determined by
1. Obtaining the factor from the transformer designer
2. Using transformer test data and the procedure in ANSI/IEEE
Standard C57.110
3. Typical values based on transformer type and size (see Table 5.2)
Exceptions. There are often cases with transformers that do not appear
to have a harmonics problem from the criteria given in Table 5.2, yet are
running hot or failing due to what appears to be overload. One common
case found with grounded-wye transformers is that the line currents
contain about 8 percent third harmonic, which is relatively low, and the
transformer is overheating at less than rated load. Why would this
transformer pass the heat run test in the factory, and, perhaps, an overload test also, and fail to perform as expected in practice? Discounting
mechanical cooling problems, chances are good that there is some conducting element in the magnetic field that is being affected by the harmonic fluxes. Three of several possibilities are as follows:
■ Zero-sequence fluxes will “escape” the core on three-legged core
designs (the most popular design for utility distribution substation
transformers). This is illustrated in Fig. 5.33. The 3d, 9th, 15th, etc.,
harmonics are predominantly zero-sequence. Therefore, if the winding
connections are proper to allow zero-sequence current flow, these harmonic fluxes can cause additional heating in the tanks, core clamps,
etc., that would not necessarily be found under balanced three-phase
or single-phase tests. The 8 percent line current previously mentioned
1 PEC R
1 K PEC R
∑ (Ih
2 h2
)
∑ Ih
2
214 Chapter Five
Fundamentals of Harmonics
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.