MDRC = Modular DIN-rail Component, SM = Surface Mounting, FM = Flush Mounting, 9
LF = Light Fitting, *PG = Price Group, **MW = Module Width 18 mm
ABB i-bus® EIB / KNX Outputs
Selection Table: Switch Actuators
SA/S
4.6.1
8.6.1
12.6.1
SA/S
2.10.1
4.10.1
8.10.1
12.10.1
SA/S
2.16.1
4.16.1
8.16.1
12.16.1
SA/S
2.16.5S
4.16.5S
8.16.5S
12.16.5
SA/S
2.20.1S
4.20.1S
8.20.1S
12.20.1
SA/M
2.6.1
Type of installation MDRC MDRC MDRC MDRC MDRC –
Rate Current In / A 6A 10AX 16A 16AX
C-Load
20AX 6AX
Current detection – – – ■1) ■1) –
Operating Voltage necessary no no no no no yes
Functions
Number of Application programs 1 11111
Switch function
– ON delay ■■■■■■
– OFF delay ■■■■■■
– Staircase lighting function ■■■■■■
– Warning before end of staircase lighting ■■■■■■
– Staircase lighting time set over object ■■■■■■
– Flashing ■■■■■■
– Switch response can be set ■■■■■■
– Threshold ■■■■■■
Current detection
– Threshold ■1) ■1)
– Current values ■1) ■1)
Scene function ■■■■■■
Logic function
– Logic object AND ■■■■■■
– Logic object OR ■■■■■■
– Logic object XOR ■■■■■■
– Gate function ■■■■■■
Priority object (positive drive) ■■■■■■
Heating actuator
– Switch ON/OFF (two-step) ■■■■■■
– Continuous control (PWM) ■■■■■■
– Cyclical fault monitoring ■■■■■■
– Automatic purging ■■■■■■
Fan coil control ■
Special function
– Default position on bus voltage failure ■■■■■■
– Status response object ■■■■■■
Switching of loads and breaking capacity
Switching load acc. AC1
EN 60947-4-1 AC3
6 A
6 A
10 A
8 A
16 A
–
16 A
16 A
20 A
16 A
6 A
6 A
Switching load acc.
EN60669
6 A
(35 uF)
10 AX
(140 uF)
16 A
(70 uF)
16 AX
(200 uF)
20 AX
(140 uF)
6 AX
(140 uF)
Mechanical contact endurance 107 3x106 3x106 106 106 3x106
Electrical endurance acc. IEC 60947-4-1
Rate current In – AC1 (240V/0.8)
Rate current In – AC3 (240V/0.45)
Rate current In – AC5a (240V/0.45)
100.000
30.000
30.000
100.000
30.000
30.000
100.000
30.000
30.000
100.000
30.000
30.000
100.000
30.000
30.000
100.000
30.000
30.000
Incandescent bulbs 1200 W 2300 W 2500 W 3680 W 3680 W 1380 W
Fluorescent lamps T5 / T8
Uncompensated
Parallel compensated
DUO-connection
800 W
300 W
350 W
2300 W
1500 W
1500 W
2500 W
1500 W
1500 W
3680 W
2500 W
3680 W
3680 W
2500 W
3680 W
1380 W
1380 W
1380 W
NV Halogen lamps
Inductive transformers
Electronic transformers
800 W
1000 W
1200 W
1500 W
1200 W
1500 W
2000 W
2500 W
2000 W
2500 W
1200 W
1380 W
Halogen lamps 230V 1000 W 2300 W 2500 W 3680 W 3680 W 1380 W
Duluxlampen (Energy saving lamps)
Uncompensated
Parallel compensated
800 W
800 W
1100 W
1100 W
1100 W
1100 W
3680 W
3000 W
3680 W
3000 W
1100 W
1100 W
Vapour lamps
Uncompensated
Parallel compensated
1000 W
800 W
2000 W
2000 W
2000 W
2000 W
3680 W
3000 W
3680 W
3000 W
1380 W
1380 W
Max. Peak Current (150 μs)
(250 μs)
200 A
160 A
400 A
320 A
400 A
320 A
600 A
480 A
600 A
480 A
400 A
320 A
Number of Electronic ballasts (T5/T8)
18 W (ABB EVG 1x18 CF) 10 23 23 262) 262) 23
24 W (ABB EVG-T5 1x24 C) 10 23 23 262) 262) 23
36 W (ABB EVG 1x36 CF) 7 14 14 22 22 14
58 W (ABB EVG 1x58 CF) 5 11 11 122) 122) 11
80 W (HELVA EL 1x80 SC) 3 10 10 102) 102) 10
1) Current detection for 2-, 4- and 8fold devices, separately per channel
2) Limited by the circuit protection device, e.g. B16 MCB