Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

transformer engineering design and practice 1_phần 1 pdf
Nội dung xem thử
Mô tả chi tiết
453
Appendix A: Fault Calculations
In this appendix, asymmetrical fault calculations for a transformer are given. A
single-line-to-ground fault on LV side is considered. The neutrals of LV and HV
windings are solidly grounded. Two distinct cases are considered, viz. with and
without fault in-feed from the secondary (LV) side. For each of these two cases, two
conditions are considered, viz. with and without stabilizing tertiary winding (TV).
The effects of omitting tertiary winding are illustrated with these cases.
Transformer Data:
Rating (S)=25 MVA, Core construction: three-phase three-limb
Voltage ratio: HV/LV/TV, 132/11/11 KV, star/star/delta
Leakage sequence impedances (based on 25 MVA base):
HV/LV:Z1=Z2=12%, Z0= 10.2%
HV/TV:Z1=Z2=20%, Z0=17.0%
LV/TV:Z1=Z2=6%, Z0=5.4%
132 KV system fault level (SF)=5000 MVA
The positive-sequence system impedance on the HV side is Z1HS=0.5% (calculated
by equation 6.2). The HV and LV side systems are assumed as effectively
grounded systems (X0/X1 not greater than 3). Here, in particular, the zero-sequence
system impedances on the LV and HV sides are assumed to be equal to the
corresponding positive-sequence system impedances for simplicity. As
mentioned earlier, two alternatives are considered for 11 KV (LV) system:
(i) Without any fault in-feed from 11 KV system.
(ii) With fault in-feed from 11 KV system:
Copyright © 2004 by Marcel Dekker, Inc.