Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

INTERNATIONAL ENERGY CONSERVATION CODE phần 7 pot
Nội dung xem thử
Mô tả chi tiết
where:
F The measured leakage rate in cfm per 100
square feet of duct surface.
P The static pressure of the test.
Documentation shall be furnished by the designer
demonstrating that representative sections totaling at
from the building exterior or unconditioned or exempt
spaces by a minimum of R-8 insulation.
Exceptions:
1. When located within equipment.
2. When the design temperature difference between
the interior and exterior ofthe duct or plenum does
not exceed 15°F (8°C).
All ducts, air handlers and filter boxes shall be sealed.
Joints and seams shall comply with Section 603.9 of the
International Mechanical Code.
503.2.7.1 Duct construction. Ductwork shall be constructed and erected in accordance with the International
Mechanical Code.
503.2.7.1.1 Low-pressure duct systems. Alliongitudinal and transverse joints, seams and connections
of supply and return ducts operating at a static pressure less than or equal to 2 inches w.g. (500 Pa) shall
be securely fastened and sealed with welds, gaskets,
mastics (adhesives), mastic-plus-embedded-fabric
systems or tapes installed in accordance with the manufacturer,s installation instructions. Pressure classifications specific to the duct system shall be clearly
indicated on the construction documents in accordance with the International Mechanical Code.
Exception: Continuously welded and locking-type longitudinal joints and seams on ducts
operating at static pressures less than 2 inches w.g.
(500 Pa) pressure classification.
503.2.7.1.2 Medium-pressure duct systems. All
ducts and plenums designed to operate at a static pressure greater than 2 inches w.g. (500 Pa) but less than 3
inches w.g. (750 Pa) shall be insulated and sealed in
accordance with Section 503.2.7. Pressure classifications specific to the duct system shall be clearly indicated on the construction documents in accordance
with the International Mechanical Code.
503.2.7.1.3 High-pressure duct systems. Ducts
designed to operate at static pressures in excess of 3
inches w.g. (746 Pa) shall be insulated and sealed in
accordance with Section 503.2.7. In addition, ducts
and plenums shall be leak-tested in accordance with
the SMACNA HVAC Air Duct Leakage Test Manual
with the rate of air leakage (CL) less than or equal to
6.0 as determined in accordance with Equation 5-2.
COMMERCIAL ENERGY EFFICIENCY
4. Spaces where the supply airflow rate
minus any makeup or outgoing transfer
air requirement is less than 1,200 cfm
(600 Lis).
503.2.6 Energy recovery ventilation systems. Individual
fan systems that have both a design supply air capacity of
5,000 cfm (2.36 m3
/s) or greater and a minimum outside air
supply of 70 percent or greater of the design supply air
quantity shall have an energy recovery system that provides
a change in the enthalpy ofthe outdoor air supply of 50 percent or more of the difference between the outdoor air and
return air at design conditions. Provision shall be made to
bypass or control the energy recovery system to permit
cooling with outdoor air where cooling with outdoor air is
required.
Exception: An energy recovery ventilation system shall
not be required in any of the following conditions:
1. Where energy recovery systems are prohibited by
the International Mechanical Code.
2. Laboratory fume hood systems that include at least
one of the following features:
2.1. Variable-air-volume hood exhaust and
room supply systems capable of reducing
exhaust and makeup air volume to 50 percent or less of design values.
2.2. Direct makeup (auxiliary) air supply equal
to at least 75 percent of the exhaust rate,
heated no warmer than 2°F (1.I OC) below
room setpoint, cooled to no cooler than 3OF
(I.7°C) above room setpoint, no
humidification added, and no simultaneous heating and cooling used for
dehumidification control.
3. Systems serving spaces that are not cooled and are
heated to less than 60°F (I5.5°C).
4. Where more than 60 percent ofthe outdoor heating
energy is provided from site-recovered or site
solar energy.
5. Heating systems in climates with less than 3,600
HDD.
6. Cooling systems in climates with a I-percent cooling design wet-bulb temperature less than 64°F
(18°C).
7. Systems requiring dehumidification that employ
series-style energy recovery coils wrapped around
the cooling coil.
503.2.7 Duct and plenum insulation and sealing. All supply and return air ducts and plenums shall be insulated with
a minimum of R-5 insulation when located in unconditioned spaces and a minimum of R-8 insulation when
located outside the building. When located within a building
envelope assembly, the duct or plenum shall be separated
CL= Fx pO.65 (Equation 5-2)
50 2009 INTERNATIONAL ENERGY CONSERVATION CODE®