Erection Bracing of Low-Rise Structural Steel Buildings phần 4 pot
MIỄN PHÍ
Số trang
10
Kích thước
157.4 KB
Định dạng
PDF
Lượt xem
1940

Erection Bracing of Low-Rise Structural Steel Buildings phần 4 pot

Nội dung xem thử

Mô tả chi tiết

Force in diagonal = 4.9 kips (47.2/40) = 5.8 kips

This force is less than the bracing force of 38 kips for

which the permanent bracing is designed.

One bolt in each angle is adequate to resist the tempo￾rary bracing force in the diagonal. The permanent brac￾ing connections are adequate by inspection.

The roof strut itself is a W24X55 spanning 40 feet. The

strut force is 4.8 kips. Per Tables 4.1 and 4.2, it can be

seen that this member is adequate to carry the strut force.

A check of PA effects is not necessary for permanent di￾agonal bracing used as part of the temporary bracing

scheme.

Lastly, the column on the compression side of the diago￾nally braced bay must be checked.

The column itself is adequate by inspection for the verti￾cal component of the temporary bracing force. This ver￾tical component is 5.8 (25/47.2) = 3.1 kips which is far

less than the column axial capacity.

4.5 Beam to Column Connections

In the typical erection process, the beam to column

connections are erected using only the minimum num￾ber of bolts required by OSHA regulations. This is done

to expedite the process of "raising" the steel in order to

minimize the use of cranes. Final bolting is not done un￾til the structure is plumbed.

In addition to the connection design strength using

the minimum fasteners, additional design strength can

be obtained by installing more fasteners up to the full de￾sign strength. This additional design strength can be in￾corporated in the temporary bracing scheme. Because

of the complexity of integrating final connections in the

temporary supports this topic is not developed in this

guide, however the principles are fully developed in

current literature such as LRFD Manual of Steel

Construction, Volume II (14) and [ASD] Manual of

Steel Construction, "Volume II – Connections" (13).

4.6 Diaphragms

Roof or floor deck can be used during the erection

process to transfer loads horizontally to vertical bracing

locations. The ability of the deck system to transfer

loads is dependent on the number and type of attach￾ments made to the supporting structure and the type and

frequency of the deck sidelap connections. Because of

the number of variables that can occur with deck dia￾phragms in practice, no general guidelines are presented

here. The designer of the temporary bracing system is

simply cautioned not to use a partially completed dia￾phragm system for load transfer until a complete analy￾sis is made relative to the partially completed dia￾phragm strength and stiffness. Evaluation of diaphragm

strength can be performed using the methods presented

in the Steel Deck Institute's "Diaphragm Design Manu￾al" (8).

5. RESISTANCE TO DESIGN LOADS —

TEMPORARY SUPPORTS

The purpose of the temporary support system is to

adequately transfer loads to the ground from their

source in the frame. Temporary support systems trans￾fer lateral loads (erection forces and wind loads) to the

ground. The principal mechanism used to do this is tem￾porary diagonal bracing, such as cables or struts, the use

of the permanent bracing or a combination thereof.

Temporary diagonal struts which carry both tension and

compression or just compression are rarely used. Cable

braces are often used. In cases when the building is

framed with multiple bays in each direction, dia￾phragms are used in the completed construction to trans￾fer lateral loads to rigid frames or braced bays. Before

the diaphragm is installed temporary supports are re￾quired in the frame lines between the frames with per￾manent bracing.

The use of cables to provide temporary lateral brac￾ing in a frame line requires that the following conditions

be met:

1. Functional strut elements (beams, joists, girders) to

transfer the lateral load to the cable braced bay.

2. Functional transfer of the lateral load into the brac￾ing tension cable and compression column pair.

3. Functional resistance of the anchorage of the cable

and the column to their respective bases and to the

ground.

27

Calculating:

The area of the frame (Af

) is computed as follows:

First frame

Thus the total frame area is:

The net area of joists is computed as:

Thus,

F at the level of the roof strut is:

Rev.

3/1/03

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.