Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

ENERGY MANAGEMENT HANDBOOKS phần 4 pptx
Nội dung xem thử
Mô tả chi tiết
HVAC SYSTEMS 265
building service personnel. For example the controls on
a unit ventilator include a room temperature thermostat
which controls the valve on the heating or cooling coil,
a damper control which adjusts the proportion of fresh
air mixed with recirculated room air, and a low-limit
thermostat which prevents the temperature of outside
air from dropping below a preset temperature (usually
55 to 60°F; 13 to 16°C). A common error of occupants or
building custodians in response to a sense that the air
supplied by the unit ventilator is too cold is to increase
the setpoint on the low-limit thermostat, which prevents
free cooling from outside air or, on systems without a
cooling coil, prevents cooling altogether. Controls which
are subject to misadjustment by building occupants
should be placed so that they cannot be tampered
with.
The energy consumption of thermally heavy
buildings is less related to either the inside or outside
air temperature. Both the heating and cooling loads in
thermally heavy buildings are heavily dependent on
the heat generated from internal loads and the thermal
energy stored in the building mass which may be disFigure 10.13 Wet-side economizer schematic diagram.
266 ENERGY MANAGEMENT HANDBOOK
sipated at a later time.
In an indirect control system the amount of energy
consumed is not a function of human thermal comfort
needs, but of other factors such as outdoor temperature, humidity, or enthalpy. Indirect control systems
determine the set points for cool air temperature, water
temperatures, etc. As a result indirect control systems
tend to adjust themselves for peak conditions rather
than actual conditions. This leads to overheating or
overcooling of spaces with less than peak loads.
One of the most serious threats to the effi ciency
of any system is the need to heat and cool air or water
simultaneously in order to achieve the thermal balance
required for adequate conditioning of spaces. Figure
10.14 indicates that 20 percent of the energy consumed
in a commercial building might be used to reheat cooled
air, offsetting another 6 percent that was used to cool the
air which was later reheated. For the example building
the energy used to cool reheated air approaches that
actually used for space cooling.
Following the 1973 oil embargo federal guidelines
encouraged everyone to reduce thermostat settings to
68°F (20°C) in winter and to increase thermostat settings
in air-conditioned buildings to 78°F (26°C) in summer.
[In 1979, the winter guideline was reduced farther to
65°F (18°C).] The effect of raising the air-conditioning
thermostat on a reheat, dual-duct, or multizone system
is actually to increase energy consumption by increasing the energy required to reheat air which has been
mechanically cooled (typically to 55°F; 13°C).
To minimize energy consumption on these types
of systems it makes more sense to raise the discharge
temperature for the cold-deck to that required to cool perimeter areas to 78°F (26°C) under peak conditions. If the
system was designed to cool to 75°F (24°C) on a peak day
using 55°F (13°C) air, the cold deck discharge could be
increased to 58°F (14.5°C) to maintain space temperatures
at no more than 78°F (26°C), saving about $5 per cfm
per year. Under less-than-peak conditions these systems
would operate more effi ciently if room temperatures were
allowed to fall below 78°F (26°C) than to utilize reheated
air to maintain this temperature.
More extensive discussion of energy management
control systems may be found in Chapters 12 and 22.
10.5.7 HVAC Equipment
The elements which provide heating and cooling
to a building can be categorized by their intended function. HVAC equipment is typically classifi ed as heating
equipment, including boilers, furnaces and unit heaters;
cooling equipment, including chillers, cooling towers
and air-conditioning equipment; and air distribution
elements, primarily air-handling units (AHUs) and fans.
A more lengthy discussion of boilers may be found
in Chapter 6, followed by a discussion of steam and
condensate systems in Chapter 7. Cooling equipment is
discussed in section 10.6, below. What follows here relates mostly to air-handling equipment and distribution
systems.
Figure 10.14 depicts the typical energy cost distribution for a large commercial building which employs an all-air reheat-type HVAC system. Excluding
the energy costs associated with lighting, kitchen and
miscellaneous loads which are typically 25-30 percent
of the total, the remaining energy can be divided into
two major categories: the energy associated with heating and cooling and the energy consumed in distribution. The total energy consumed for HVAC systems
is therefore dependent on the effi ciency of individual
components, the effi ciency of distribution and the ability
of the control system to accurately regulate the energy
consuming components of the system so that energy is
not wasted.
The size (and heating, cooling, or air-moving capacity) of HVAC equipment is determined by the mechanical designer based upon a calculation of the peak
internal and envelope loads. Since the peak conditions
are arbitrary (albeit well-considered and statistically
valid) and it is likely that peak loads will not occur
simultaneously throughout a large building or complex
Figure 10.14 Energy cost distribution for a typical
non-residential building using an all-air reheat HVAC
system.
Space
cooling
Other
uncertain)
(magnitude
Kitchen
& process
Domestic
hot water
Cooling of reheat
Pumps
Fans
Lighting
Reheat
Space heating
HVAC SYSTEMS 267
requiring all equipment to operate at its rated capacity,
it is common to specify equipment which has a total
capacity slightly less than the peak requirement. This
diversity factor varies with the function of the space.
For example, a hospital or classroom building will use
a higher diversity multiplier than an offi ce building.
In sizing heating equipment however, it is not uncommon to provide a total heating capacity from several
units which exceeds the design heating load by as much
as fi fty percent. In this way it is assured that the heating
load can be met at any time, even in the event that one
unit fails to operate or is under repair.
The selection of several boilers, chillers, or airhandling units whose capacities combine to provide
the required heating and cooling capability instead of
single large units allows one or more components of
the system to be cycled off when loads are less than the
maximum.
This technique also allows off-hours use of specifi c
spaces without conditioning an entire building.
Equipment Effi ciency
Effi ciency, by defi nition, is the ratio of the energy
output of a piece of equipment to its energy input, in
like units to produce a dimensionless ratio. Since no
equipment known can produce energy, effi ciency will
always be a value less than 1.0 (100%).
Heating equipment which utilizes electric resistance appears at first glance to come closest to the
ideal of 100 percent effi ciency. In fact, every kilowatt of
electrical power consumed in a building is ultimately
converted to 3413 Btu per hour of heat energy. Since this
is a valid unit conversion it can be said that electric resistance heating is 100 percent effi cient. What is missing
from the analysis however, is the ineffi ciency of producing electricity, which is most commonly generated using
heat energy as a primary energy source.
Electricity generation from heat is typically about
30 percent effi cient, meaning that only 30 percent of the
heat energy is converted into electricity, the rest being
dissipated as heat into the environment. Energy consumed as part of the generation process and energy lost
in distribution use up about ten percent of this, leaving
only 27 percent of the original energy available for use
by the consumer. By comparison, state-of-the-art heating
equipment which utilizes natural gas as a fuel is more
than eighty percent effi cient. Distribution losses in natural gas pipelines account for another 5 percent, making
natural gas approximately three times as effi cient as a
heat energy source than electricity.
The relative efficiency of cooling equipment is
usually expressed as a coeffi cient of performance (COP),
which is defi ned as the ratio of the heat energy extracted
to the mechanical energy input in like units. Since the
heat energy extracted by modem air conditioning far
exceeds the mechanical energy input a COP of up to 6
is possible.
Air-conditioning equipment is also commonly
rated by its energy effi ciency ratio (EER) or seasonal energy effi ciency ratio (SEER). EER is defi ned as the ratio
of heat energy extracted (in Btu/hr) to the mechanical
energy input in watts. Although it should have dimensions of Btu/hr/watt, it is expressed as a dimensionless
ratio and is therefore related to COP by the equation
EER = 3.41 • COP (10.4)
Although neither COP nor EER is the effi ciency
of a chiller or air-conditioner, both are measures which
allow the comparison of similar units. The term air-conditioning effi ciency is commonly understood to indicate
the extent to which a given air-conditioner performs to
its maximum capacity. As discussed below, most equipment does not operate at its peak effi ciency all of the
time. For this reason, the seasonal energy effi ciency ratio
(SEER), which takes varying effi ciency at partial load
into account, is a more accurate measure of air-conditioning effi ciency than COP or EER.
In general, equipment effi ciency is a function of
size. Large equipment has a higher effi ciency than small
equipment of similar design. But the rated effi ciency of
this equipment does not tell the whole story. Equipment
effi ciency varies with the load imposed. All equipment
operates at its optimum effi ciency when operated at or
near its design full-load condition. Both overloading
and under-loading of equipment reduces equipment effi ciency.
This fact has its greatest impact on system effi ciency when large systems are designed to air-condition an
entire building or a large segment of a major complex.
Since air-conditioning loads vary and since the design
heating and cooling loads occur only rarely under the
most severe weather or occupancy conditions, most of
the time the system must operate under-loaded. When
selected parts of a building are utilized for off-hours
operation this requires that the entire building be conditioned or that the system operate far from its optimum
conditions and thus at far less than its optimum effi -
ciency.
Since most heating and cooling equipment operates at less than its full rated load during most of the
year, its part-load effi ciency is of great concern. Because
of this, most state-of-the-art equipment operates much
closer to its full-load effi ciency than does older equip-
268 ENERGY MANAGEMENT HANDBOOK
ment. A knowledge of the actual operating effi ciency of
existing equipment is important in recognizing economic opportunities to reduce energy consumption through
equipment replacement.
Distribution Energy
Distribution energy is most commonly electrical
energy consumed to operate fans and pumps, with fan
energy typically being far greater than pump energy except in all-water distribution systems. The performance
of similar fans is related by three fan laws which relate
fan power, airfl ow, pressure and effi ciency to fan size,
speed and air density. The reader is referred to the
ASHRAE Handbook: HVAC Systems and Equipment for
additional information on fans and the application of
the fan laws.3
Fan energy is a function of the quantity of airfl ow
moved by the fan, the distance over which it is moved,
and the velocity of the moving air (which infl uences
the pressure required of the fan). Most HVAC systems,
whether central or distributed packaged systems, allair, all-water, or a combination are typically oversized
for the thermal loads that actually occur. Thus the fan
is constantly required to move more air than necessary,
creating inherent system ineffi ciency.
One application of the third fan law describes
the relationship between fan horsepower (energy consumed) and the airfl ow produced by the fan:
W1 = W2 × (Q1/Q2)3 (10.5)
where
W = fan power required, hp
Q = volumetric fl ow rate, cfm
Because fan horsepower is proportional to the cube
of airfl ow, reducing airfl ow to 75 percent of existing
will result in a reduction in the fan horsepower by the
cube of 75 percent, or about 42 percent: [(0.75)3 = 0.422]
Even small increases in airfl ow result in disproportional
increases in fan energy. A ten percent increase in airfl ow
requires 33 percent more horsepower [1.103 = 1.33],
which suggests that airfl ow supplied solely for ventilation purposes should be kept to a minimum.
All-air systems which must move air over great
distances likewise require disproportionate increases in
energy as the second fan law defi nes the relationship
between fan horsepower [W] and pressure [p], which
may be considered roughly proportional to the length
of ducts connected to the fan:
W1 = W2 × (P1/P1)3/2 (10.6)
The use of supply air at temperatures of less than
55°F (13°C) for primary cooling air permits the use of
smaller ducts and fans, reducing space requirements
at the same time. This technique requires a complex
analysis to determine the economic benefi t and is seldom advantageous unless there is an economic benefi t
associated with space savings.
System Modifi cations
In examining HVAC systems for energy conservation opportunities, the less effi cient a system is, the
greater is the potential for signifi cant conservation to
be achieved. There are therefore several “off-the-shelf”
opportunities for improving the energy efficiency of
selected systems.
All-air Systems—Virtually every type of all-air
system can benefi t from the addition of an economizer
cycle, particularly one with enthalpy controls. Systems
with substantial outside air requirements can also benefi t from heat recovery systems which exchange heat
between exhaust air and incoming fresh air. This is a
practical retrofi t only when the inlet and exhaust ducts
are in close proximity to one another.
Single zone systems, which cannot provide sufficient control for varying environmental conditions
within the area served can be converted to variable air
volume (VAV) systems by adding a VAV terminal and
thermostat for each new zone. In addition to improving
thermal comfort this will normally produce a substantial
saving in energy costs.
VAV systems which utilize fans with inlet vanes
to regulate the amount of air supplied can benefi t from
a change to variable speed or variable frequency fan
drives. Fan effi ciency drops off rapidly when inlet vanes
are used to reduce airfl ow.
In terminal reheat systems, all air is cooled to
the lowest temperature required to overcome the peak
cooling load. Modern “discriminating” control systems
which compare the temperature requirements in each
zone and cool the main airstream only to the temperature required by the zone with the greatest requirements
will reduce the energy consumed by these systems.
Reheat systems can also be converted to VAV systems
which moderate supply air volume instead of supply air
temperature, although this is a more expensive alteration than changing controls.
Similarly, dual-duct and multizone systems can benefi t from “smart” controls which reduce cooling requirements by increasing supply air temperatures. Hot-deck
temperature settings can be controlled so that the temperature of warm supply air is just high enough to meet
HVAC SYSTEMS 269
design heating requirements with 100 percent hot-deck
supply air and adjusted down for all other conditions
until the hot-deck temperature is at room temperature
when outside temperatures exceed 75°F (24°C). Dual duct
terminal units can be modifi ed for VAV operation.
An economizer option for multizone systems is
the addition of a third “bypass” deck to the multizone
air-handling unit. This is not appropriate as a retrofi t
although an economizer can be utilized to provide colddeck air as a retrofi t.
All-water systems—Wet-side economizers are the
most attractive common energy conservation measure
appropriate to chilled water systems. Hot-water systems
benefi t most from the installation of self-contained thermostat valves, to create heating zones in spaces formerly
operated as single-zone heating systems.
Air-water Induction—Induction systems are seldom installed anymore but many still exist in older
buildings. The energy-effi ciency of induction systems
can be improved by the substitution of fan-powered
VAV terminals to replace the induction terminals.
10.6 COOLING EQUIPMENT
The most common process for producing cooling
is vapor-compression refrigeration, which essentially
moves heat from a controlled environment to a warmer,
uncontrolled environment through the evaporation of
a refrigerant which is driven through the refrigeration
cycle by a compressor.
Vapor compression refrigeration machines are
typically classified according to the method of operation of the compressor. Small air-to-air units most
commonly employ a reciprocating or scroll compressor, combined with an air-cooled condenser to form
a condensing unit. This is used in conjunction with a
direct-expansion (DX) evaporator coil placed within
the air-handling unit.
Cooling systems for large non-residential buildings
typically employ chilled water as the medium which
transfers heat from occupied spaces to the outdoors
through the use of chillers and cooling towers.
10.6.1 Chillers
The most common type of water chiller for large
buildings is the centrifugal chiller which employs a
centrifugal compressor to compress the refrigerant,
which extracts heat from a closed loop of water which is
pumped through coils in air-handling or terminal units
within the building. Heat is rejected from the condenser
into a second water loop and ultimately rejected to the
environment by a cooling tower.
The operating fl uid used in these chillers may be
either a CFC or HCFC type refrigerant. Many existing
centrifugal chillers use CFC-11 refrigerants, the manufacture and use of which is being eliminated under the
terms of the Montreal Protocol. New refrigerants HCFC123 and HCFC-134a are being used to replace the CFC
refrigerants but refrigerant modifications to existing
equipment will reduce the overall capacity of this equipment by 15 to 25 percent.
Centrifugal chillers can be driven by open or
hermetic electric motors or by internal combustion
Table 10.1 Summary of HVAC System Modifi cations for Energy Conservation
System type Energy Conservation Opportunities
All-air systems (general): economizer
heat recovery
Single zone systems conversion to VAV
Variable air volume (VAV) systems replace fan inlet vane control with variable frequency drive fan
Reheat systems use of discriminating control systems
conversion to VAV
Constant volume dual-duct systems use of discriminating control systems
conversion to dual duct VAV
Multizone systems use of discriminating control systems
addition of by-pass deck*
All-water systems:
hydronic heating systems addition of thermostatic valves
chilled water systems wet-side economizer
Air-water induction systems replacement with fan-powered VAV terminals
*Requires replacement of air-handling unit
270 ENERGY MANAGEMENT HANDBOOK
engines or even by steam or gas turbines. Natural gas
engine-driven equipment sized from 50 to 800 tons of
refrigeration are available and in some cases are used to
replace older CFC-refrigerant centrifugal chillers. These
engine-driven chillers are viable when natural gas costs
are suffi ciently low. Part-load performance modulates
both engine speed and compressor speed to match the
load profi le, mainta ining close to the peak effi ciency
down to 50 percent of rated load. They can also use heat
recovery options to take advantage of the engine jacket
and exhaust heat.
Turbine-driven compressors are typically used on
very large equipment with capacities of 1200 tons or
more. The turbine may be used as part of a cogeneration
process but this is not required. (For a detailed discussion of cogeneration, see Chapter 7.) If excess steam is
available, in industry or a large hospital, a steam turbine
can be used to drive the chiller. However the higher load
on the cooling tower due to the turbine condenser must
be considered in the economic analysis.
Small water chillers, up to about 200 tons of capacity, may utilize reciprocating or screw compressors and
are typically air-cooled instead of using cooling towers.
An air-cooled chiller uses a single or multiple compressors to operate a DX liquid cooler. Air-cooled chillers are
widely used in commercial and large-scale residential
buildings.
Other types of refrigeration systems include liquid
overfeed systems, fl ooded coil systems and multi-stage
systems. These systems are generally used in large industrial or low-temperature applications.
10.6.2 Absorption Chillers
An alternative to vapor-compression refrigeration
is absorption refrigeration which uses heat energy to
drive a refrigerant cycle, extracting heat from a controlled environment and rejecting it to the environment
(Figure 10.15). Thirty years ago absorption refrigeration
was known for its low coeffi cient of performance and
high maintenance requirements. Absorption chillers
used more energy than centrifugal chillers and were
economical only if driven by a source of waste heat.
Today, due primarily to the restriction on the use
of CFC and HCFC refrigerants, the absorption chiller
is making a comeback. Although new and improved, it
still uses heat energy to drive the refrigerant cycle and
typically uses aqueous lithium bromide to absorb the
refrigerant and water vapor in order to provide a higher
coeffi cient of performance.
The new absorption chillers can use steam as a
heat source or be direct-fi red. They can provide simultaneous heating and cooling which eliminates the need
for a boiler. They do not use CFC or HCFC refrigerants,
which may make them even more attractive in years
to come. Improved safety and controls and better COP
(even at part load) have propelled absorption refrigeration back into the market.
In some cases, the most effective use of refrigeration equipment in a large central-plant scenario is
to have some of each type, comprising a hybrid plant.
From a mixture of centrifugal and absorption equipment the operator can determine what equipment will
provide the lowest operating cost under different conFigure 10.15 Simplifi ed absorption cycle schematic diagram.
HVAC SYSTEMS 271
ditions. For example a hospital that utilizes steam year
round, but at reduced rates during summer, might use
the excess steam to run an absorption chiller or steamdriven turbine centrifugal chiller to reduce its summertime electrical demand charges.
10.6.3 Chiller Performance
Most chillers are designed for peak load and then
operate at loads less than the peak most of the time.
Many chiller manufacturers provide data that identifi es
a chiller’s part-load performance as an aid to evaluating energy costs. Ideally a chiller operates at a desired
temperature difference (typically 45-55 degrees F; 25-30
degrees C) at a given fl ow rate to meet a given load.
As the load requirement increases or decreases, the
chiller will load or unload to meet the need. A reset
schedule that allows the chilled water temperature to
be adjusted to meet thermal building loads based on
enthalpy provides an ideal method of reducing energy
consumption.
Chillers should not be operated at less than 50 percent of rated load if at all possible. This eliminates both
surging and the need for hot-gas bypass as well as the
potential that the chiller would operate at low effi ciency.
If there is a regular need to operate a large chiller at less
than one-half of the rated load it is economical to install
a small chiller to accommodate this load.
10.6.4 Thermal Storage
Thermal storage can be another effective way of
controlling electrical demand by using stored chilled
water or ice to offset peak loads during the peak demand time. A good knowledge of the utility consumption and/or load profi le is essential in determining the
applicability of thermal storage. See Chapter 19 for a
discussion of thermal storage systems.
10.6.5 Cooling Towers
Cooling towers use atmospheric air to cool the
water from a condenser or coil through evaporation. In
general there are three types of cooling tower, named for
the relationship between the fan-powered airfl ow and the
fl ow of water in the tower: counterfl ow induced draft,
crossfl ow induced draft and counterfl ow forced draft.
The use of variable-speed, two-speed or three-speed
fans is one way to optimize the control of the cooling
tower in order to reduce power consumption and provide
adequate water cooling capacity. As the required cooling
capacity increases or decreases the fans can be sequenced
to maintain the approach temperature difference. For
most air-conditioning systems this usually varies between
5 and 12 degrees F (3 to 7 degrees C).
When operated in the winter, the quantity of air
must be carefully controlled to the point where the
water spray is not allowed to freeze. In cold climates it
may be necessary to provide a heating element within
the tower to prevent freeze-ups. Although electric resistance heaters can be used for this purpose it is far more
effi cient to utilize hot water or steam as a heat source if
available.
10.6.6 Wet-side Economizer
The use of “free-cooling” using the cooling tower
water to cool supply air or chilled water is referred to
as a wet-side economizer. The most common and effective way of interconnecting the cooling tower water to
the chilled water loop is through the use of a plate-andframe heat exchanger which offers a high heat transfer
rate and low pressure drop. This method isolates the
cooling tower water from the chilled water circuit maintaining the integrity of the closed chilled water loop.
Another method is to use a separate circuit and pump
that allows cooling tower w ater to be circulated through
a coil located within an air-handling unit.
The introduction of cooling tower water, into
the chilled water system, through a so-called strainer
cycle, can create maintenance nightmares and should
be avoided. The water treatment program required for
chilled water is intensive due to the required cleanness
of the water in the chilled water loop.
10.6.7 Water treatment
A good water treatment program is essential to
the maintenance of an effi cient chilled water system.
Filtering the cooling tower water should be evaluated.
In some cases, depending on water quality, this can save
the user a great deal of money in chemicals. Pretreating
new system s prior to initial start-up will also provide
longer equipment life and insure proper system performance.
Chiller performance is based on given design parameters and listed in literature provided by the chiller
manufacturer. The performance will vary with building
load, chilled water temperature, condenser water temperature and fouling factor. The fouling factor is the resistance caused by dirt, scale, silt, rust and other deposits
on the surface of the tubes in the chiller and signifi cantly
affects the overall heat transfer of the chiller.
10.7 DOMESTIC HOT WATER
The creation of domestic hot water (DHW) represents about 4 percent of the annual energy consumption
272 ENERGY MANAGEMENT HANDBOOK
in typical non-residential buildings. In buildings where
sleeping or food preparation occur, including hotels,
restaurants, and hospitals, DHW may account for as
much as thirty percent of total energy consumption.
Some older lavatory faucets provide a fl ow of 4 to 6
gal/min (0.25 to 0.38 l/s). Since hand washing is a function more of time than water use, substantial savings can
be achieved by reducing water fl ow. Reduced-fl ow faucets which produce an adequate spray pattern can reduce
water consumption to less than 1 gal/min (0.06 l/s). Flow
reducing aerator replacements are also available.
Reducing DHW temperature has also been shown
to save energy in non-residential buildings. Since most
building users accept water at the available temperature, regardless of what it is, water temperature can be
reduced from the prevailing standard of 140°F (60°C)
to a 105°F (40°C) utilization temperature saving up to
one-half of the energy used to heat the water.
Many large non-commercial buildings employ recirculating DHW distribution systems in order to reduce
or eliminate the time required and water wasted in
fl ushing cold water from hot water piping. Recirculating
distribution is economically attractive only where DHW
use is high and/or the cost of water greatly exceeds the
cost of water heating. In most cases the energy required
to keep water in recirculating DHW systems hot exceeds
the energy used to heat the water actually used.
To overcome this waste of energy there is a trend
to convert recirculating DHW systems to localized pointof-use hot water heating, particularly in buildings where
plumbing facilities are widely separated. In either case
insulation of DHW piping is essential in reducing the
waste of energy in distribution. One-inch of insulation
on DHW pipes will result in a 50% reduction in the
distribution heat loss.
One often-overlooked energy conservation opportunity associated with DHW is the use of solar-heated
hot water. Unlike space-heating, the need for DHW is
relatively constant throughout the year and peaks during hours of sunshine in non-residential buildings. Yearround use amortizes the cost of initial equipment faster
than other active-solar options.
Many of the techniques appropriate for reducing
energy waste in DHW systems are also appropriate for
energy consumption in heated service water systems for
industrial buildings or laboratories.
10.8 ESTIMATING HVAC
ENERGY CONSUMPTION
The methods for estimating building heating and
cooling loads and the consumption of energy by HVAC
systems are described in Chapter 9.
References
1. ASHRAE Handbook: Fundamentals, American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc., Atlanta,
1993.
2. ASHRAE Handbook: HVAC Applications, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta,
1995.
3. ASHRAE Handbook: HVAC Systems and Equipment, American Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc., Atlanta, 1992.
4. ASHRAE Handbook: Refrigeration, American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc., Atlanta,
1 9 9 4 .
K.K. LOBODOVSKY
BSEE & BSME
Certifi ed Energy Auditor
State of California
11.1 INTRODUCTION
Effi cient use of electric energy enables commercial,
industrial and institutional facilities to minimize operating costs, and increase profi ts to stay competitive.
The majority of electrical energy in the United
States is used to run electric motor driven systems.
Generally, systems consist of several components, the
electrical power supply, the electric motor, the motor
control, and a mechanical transmission system.
There are several ways to improve the systems'
effi ciency. The cost effective way is to check each component of the system for an opportunity to reduce electrical losses. A qualifi ed individual should oversee the
electrical system since poor power distribution within a
facility is a common cause of energy losses.
Technology Update Ch. 181 lists 20 items to help
facility management staff identify opportunities to improve drive system effi ciency.
1. Maintain Voltage Levels.
2. Minimize Phase Imbalance.
3. Maintain Power Factor.
4. Maintain Good Power Quality.
5. Select Effi cient Transformers.
6. Identify and Fix Distribution System Losses.
7. Minimize Distribution System Resistance.
8. Use Adjustable Speed Drives (ASDs) or 2-Speed
Motors Where Appropriate.
9. Consider Load Shedding.
10. Choose Replacement Before a Motor Fails.
11. Choose Energy-Effi cient Motors.
12. Match Motor Operating Speeds.
13. Size Motors for Effi ciency.
14. Choose 200 Volt Motors for 208 Volt Electrical Systems.
15. Minimize Rewind Losses.
16. Optimize Transmission Effi ciency.
17. Perform Periodic Checks.
18. Control Temperatures.
19. Lubricate Correctly.
20. Maintain Motor Records.
Some of these steps require the one-time involvement of an electrical engineer or technician. Some
steps can be implemented when motors fail or major
capital changes are made in the facility. Others involve
development of a motor monitoring and maintenance
program.
11.2 POWER SUPPLY
Much of this information consists of standards
defi ned by the National Electrical Manufacturers Association (NEMA).
The power supply is one of the major factors affecting selection, installation, operation, and maintenance
of an electrical motor driven system. Usual service conditions, defi ned in NEMA Standard Publication MG1,
Motors and Generators,
2 include:
• Motors designed for rated voltage, frequency, and
number of phases.
• The supply voltage must be known to select the
proper motor.
• Motor nameplate voltage will normally be less
then nominal power system voltage.
Nominal Motor Utilization
Power System (Nameplate) Voltage
Voltage (Volts) Volts ——————— ——————————
208 200
240 230
480 460
600 575
2400 2300
4160 4000
6900 6600
13800 13200
• Operation within tolerance of ±10 percent of the
rated voltage.
CHAPTER 11
ELECTRIC ENERGY MANAGEMENT
273