Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

Control Engineering - A guide for beginners - Chapter 6 doc
Nội dung xem thử
Mô tả chi tiết
JUMO, FAS 525, Edition 02.04 101
6 Improved control quality through special controls
So far, we have only considered single-loop control circuits, where controller and process form a
closed signal loop. However, when using such single-loop control circuits, there are limits to the
control quality which can be achieved in certain control processes. It is possible to go beyond the
control quality limits imposed by the single-loop control circuit by using multi-loop control circuits,
or by switching auxiliary variables on and off. To some extent, relatively simple solutions can lead
to considerable improvements in control quality.
6.1 Base load
With a base load setting, the controller only influences part of the total manipulating variable, and a
fixed proportion is continuously supplied to the process (combination of control and operation). It
could then be the case that, for example in an electrically heated furnace, one section of the heating elements is controlled by the controller, whereas another section is supplied at full supply voltage (see Fig. 65).
Fig. 65: Base load setting
Essentially, base load setting offers the following advantages:
- The actuator, e.g. a thyristor controller, can be more compact and less expensive, as it only
needs to control low power.
- Load fluctuations on the supply network, as a result of power consumption in bursts caused by
the switching controller, are similarly reduced.
- If the controller fails, the process can still be operated with the base load component of the total
power.
Furnace
R1
K1
N
L1
x
t
100 % power
with base load
without base load
R2
6 Improved control quality through special controls
102 JUMO, FAS 525, Edition 02.04
Against the advantages shown, there are also a number of disadvantages:
- The dynamic control action is impaired, especially with regard to disturbances. As the controller
now no longer provides the full manipulating variable, the cooling curve, for instance, is not only
shifted by the amount of the base load setting, but is also clearly flatter (see Fig. 65). If, for any
reason, the power requirement suddenly becomes less than the base load setting, the controller
is helpless in this situation, as it cannot reduce the manipulating variable below the value of the
base load.
- In addition, the base load setting must also be matched to the setpoint. If the setpoint is
changed downwards, for instance, the excess power could suddenly be too large; with an
upward change, the excess power could be too small. In such cases, the base load should be
changed at the same time as the setpoint.