Thư viện tri thức trực tuyến
Kho tài liệu với 50,000+ tài liệu học thuật
© 2023 Siêu thị PDF - Kho tài liệu học thuật hàng đầu Việt Nam

A Guide to BS EN 62305:2006 Protection Against Lightning Part 6 pps
Nội dung xem thử
Mô tả chi tiết
If the metallic and electrical services enter the
structure at different locations and thus several
bonding bars are required, these bonding bars should
be connected directly to the earth termination system,
which preferably should be a ring (Type B) earth
electrode arrangement.
If a Type A earth electrode arrangement is used then
the bonding bars should be connected to an individual
earth electrode (rod) and additionally interconnected
by an internal ring conductor.
If the services enter the structure above ground level,
the bonding bars should be connected to a horizontal
ring conductor either inside or outside the outer wall
and in turn be bonded to the external down
conductors and reinforcing bars of the structure.
Where structures are typically computer centres or
communication buildings where a low induced
electromagnetic field is essential, then the ring
conductors should be bonded to the reinforcing bars
approximately every 5 metres.
Protection measures for roof mounted equipment
containing electrical equipment
This is an issue that has already caused some debate.
Applying the guidance from BS 6651 the
designer/installer would bond the metallic, roof
mounted casing into the mesh air termination system
and accept that if the metallic casing suffered a direct
lightning strike, then the casing, if not sufficiently
thick, could be punctured.
What it did not address to any great degree was the
solution to the possibility of partial lightning currents
or induced overvoltages entering into the structure,
via any metallic services that were connected to the
roof mounted equipment.
BS EN 62305-3 significantly elaborates this topic.
Our interpretation of the lightning protection
requirements can be summarised by the flow chart
shown in Figure 4.41.
There are several scenarios that can occur:
a) If the roof mounted equipment is not protected
by the air termination system but can withstand a
direct lightning strike without being punctured,
then the casing of the equipment should be
bonded directly to the LPS. If the equipment has
metallic services entering the structure (gas, water
etc) that can be bonded directly, then these should
be bonded to the nearest equipotential bonding
bar. If the service cannot be bonded directly
(power, telecom, cables) then the ‘live’ cores
should be bonded to the nearest equipotential
bonding bar, via suitable Type I lightning current
SPDs.
BS EN 62305-3 | Lightning equipotential bonding
64
www.furse.com
b) If the roof mounted equipment cannot withstand
a direct lightning strike then a separation
(ie isolation) distance needs to be calculated
(explained in more detail, later in this section). If
this separation distance can be achieved, (ie there
is sufficient space on the roof) then an air rod or
suspended conductor should be installed (see
Figure 4.19). This should offer sufficient protection
via the protective angle or rolling sphere method
and is so spaced from the equipment, such that it
complies with the separation distance. This air
rod/suspended conductor should form part of the
air termination system. If the equipment has
metallic services entering the structure (gas, water
etc) that can be bonded directly, then these should
be bonded to the nearest equipotential bonding
bar. If the other electrical services do not have an
effective outer core screen, then consideration
should be given to bonding to the nearest
equipotential bonding bar, via Type II overvoltage
SPDs.
If the electrical services are effectively screened
but are supplying electronic equipment, then
again due consideration should be given to
bonding, via Type II overvoltage SPDs.
If the electrical services are effectively screened
but are not supplying electronic equipment, then
no additional measures are required.
c) If the roof mounted equipment cannot withstand
a direct lightning strike, then again a separation
distance needs to be calculated. If this separation
distance cannot practically be achieved, (ie there is
insufficient space on the roof) then an air rod or
suspended conductor should be installed. This still
needs to meet the protective angle or rolling
sphere criteria but this time, there should be a
direct bond to the casing of the equipment.
Again, the air rod/suspended conductor should
be connected into the air termination system.
If the equipment has metallic services entering
the structure (gas, water etc) that can be bonded
directly, then these should be bonded to the
nearest equipotential bonding bar. If the service
cannot be bonded directly, (power, telecom,
cables) then the ‘live’ cores should be bonded to
the nearest equipotential bonding bar, via suitable
Type I lightning current SPDs.
The above explanation/scenarios are somewhat
generic in nature and clearly the ultimate protection
measures will be biased to each individual case.
We believe the general principle of offering air
termination protection, wherever and whenever
practical, alongside effective equipotential bonding
and the correct choice of SPDs where applicable, are
the important aspects to be considered when deciding
on the appropriate lightning protection measures.
BS EN 62305-3 Physical damage to
structures and life hazard